Thank you for taking an interest in our selection of 5925-00-320-7551 parts here on Boost AOG. You are currently on the RFQ form for part number S372D300G13, a Westinghouse Electric Corp product listed with the Circuitbreaker If part number S372D300G13 catches your eye, be sure to use our online RFQ service to request quotes, with customized responses provided within 15 minutes of us receiving and reviewing a completed submission.
Note : We Will Not Share Your Information To Any Third Parties.
To ensure the quality of our NSN components, we adhere to a strict NO CHINA SOURCING pledge, meaning every purchased item will be delivered alongside any pertinent qualifying certifications or manufacturing trace documentation for your benefit. Paired with numerous other commitments, we proudly operate with AS9120B, ISO 9001:2015, and FAA AC 00-56B accreditation. If you happen to be facing a time constraint and require NSN parts quickly, contact us at your earliest convenience, and we will discuss the expedited shipping options we have available for domestic and international customers alike. With our various dedications in mind, kick off procurement for Westinghouse Electric Corp part number S372D300G13 and other Circuitbreaker products today.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-320-7551 Item PartTypeName: CIRCUIT BREAKER | 5925 | 003207551 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | U | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
370D876G13 | 2 | 9 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPE |
ADAQ | BODY LENGTH | 10.750 INCHES NOMINAL |
ADAT | BODY WIDTH | 8.250 INCHES NOMINAL |
ADAU | BODY HEIGHT | 4.062 INCHES NOMINAL |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 9.531 INCHES NOMINAL |
AEBQ | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 2.750 INCHES NOMINAL |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.312 INCHES NOMINAL |
AEBY | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 9.531 INCHES NOMINAL |
AEHA | DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 2.750 INCHES NOMINAL |
AJEC | BOSS HEIGHT | 0.250 INCHES NOMINAL |
AKPX | POLE QUANTITY | 2 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 400.0 AMPERES AC AND 400.0 AMPERES DC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 600.0 AC AND 250.0 DC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 25000.0 AC AND 10000.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | BETWEEN POLE ONE AND TWO |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 90.000 MINIMUM AT 200 PCT AND 550.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS MAXIMUM ALL LOCATIONS |
CWJK | CASE MATERIAL | PLASTIC |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
TTQY | TERMINAL TYPE AND QUANTITY | 4 SCREW |