Thank you for taking an interest in our selection of 5925-00-208-4081 parts here on Boost AOG. You are currently on the RFQ form for part number KAL36125, a Square D Company product listed with the Circuit Breaker If part number KAL36125 catches your eye, be sure to use our online RFQ service to request quotes, with customized responses provided within 15 minutes of us receiving and reviewing a completed submission.
Note : We Will Not Share Your Information To Any Third Parties.
To ensure the quality of our NSN components, we adhere to a strict NO CHINA SOURCING pledge, meaning every purchased item will be delivered alongside any pertinent qualifying certifications or manufacturing trace documentation for your benefit. Paired with numerous other commitments, we proudly operate with AS9120B, ISO 9001:2015, and FAA AC 00-56B accreditation. If you happen to be facing a time constraint and require NSN parts quickly, contact us at your earliest convenience, and we will discuss the expedited shipping options we have available for domestic and international customers alike. With our various dedications in mind, kick off procurement for Square D Company part number KAL36125 and other Circuit Breaker products today.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-208-4081 Item Description: Circuit Breaker | 5925 | 002084081 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | U | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Kal36125 | 2 | 9 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
MRC | Decoded Requirement | Clear Text Reply |
AEBY | Distance Between Centerlines Of Mounting Facilities Parallel To Body Length | 7.125 INCHES NOMINAL |
AKPX | Pole Quantity | 3 |
CPRF | Operating Voltage Type And Rating Per Pole In Volts | 600.0 AC ALL LOCATIONS |
CPRG | Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 30000.0 AC ALL LOCATIONS |
CPRJ | Trip Release Method | THERMAL-MAGNETIC ALL LOCATIONS |
CPRH | Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
FREQ | Frequency In Hertz | 60.0 ALL LOCATIONS |
CPRN | Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 138.0 ALL LOCATIONS |
AEHA | Distance Between Centerlines Of Mounting Facilities Parallel To Body Width | 1.500 INCHES NOMINAL |
CRCF | Trip Release Ambient Temp Rating | 40.0 DEG CELSIUS MAXIMUM ALL LOCATIONS |
AJEC | Boss Height | 0.125 INCHES NOMINAL |
CPRQ | Reset Method | MANUAL |
CPRT | Manual Actuator Type And Quantity | 1 TOGGLE |
AXHR | Mounting Facility Type And Quantity | 4 UNTHREADED HOLE |
CPRX | Actuator Position Designation | AT POLE TWO |
CPRR | Main Contact Tripping Mechanism Type | TRIP FREE |
ADTV | Case Material | PLASTIC |
ADAT | Body Width | 4.500 INCHES NOMINAL |
ADAQ | Body Length | 8.000 INCHES NOMINAL |
AEBP | Center To Center Distance Between Terminals Parallel To Length | 6.562 INCHES NOMINAL |
ADAU | Body Height | 3.500 INCHES NOMINAL |
CPLM | Maximum Continuous Load Current Rating Per Pole | 125.0 AMPERES AC ALL LOCATIONS |
AAQL | Body Style | MULTIPOLE-SINGLE ACTUATOR TYPE |
AEBQ | Center To Center Distance Between Terminals Parallel To Width | 1.500 INCHES NOMINAL |
CQWN | Trip Delay Time In Seconds Per Rated Continuous Current | 150.000 MINIMUM AT 200 PCT AND |
CQWN | Trip Delay Time In Seconds Per Rated Continuous Current | 275.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CPRL | Trip Release Characteristic | TIME DELAY ALL LOCATIONS |
AEBV | Unthreaded Mounting Hole Diameter | 0.201 INCHES NOMINAL |
CPRW | Actuator Function | TRIP-RESET |
TTQY | Terminal Type And Quantity | 6 COMPRESSION |